• The FC726-ZA (4-loop, expandable to 28 loops) is a modular fire control panel with an integrated operating unit tha The fire control panel can be used as a stand-alone version or networked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility.
• Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.
• All detector lines are monitored for ground faults.
• Adaptation of the user text directly on the terminal or with the software engineering tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.
• Detection and automatic read-in (auto configuration) of all C-NET devices� providing immediate simple operation.
• Stored data can be uploaded via Cerberus-Remote access.
• The FC726 is ideally suited for veryt can process signals from Cerberus PRO devices of up to 1512 addresses. A card cage in the basic fire control panel equipment is used for installation of additional line cards (C-NET) or I/O cards. A mix of up to 5 cards max. is possible. Line and I/O cards can be exchanged without removing power from control panel.
• For the large and complex buildings, eg. Office buildings, university campuses, etc. The FC726-ZA with flexible cross linking possibilities can also be used for extensive systems. The expansion and accessories must be ordered separately.
Date Tehnice
• Detector compatibility: Cerberus PRO FD720
• Number of addresses: max. 1512
• Number of detector lines: Loop with loop extension -> 4 loops or 8 stub lines C-NET -> max. 20 (4 per line card)
• Programmable input/output: max. 60 (12 per card)
• Supervised output: 1 x RT alarm; 1 x RT fault 2 x Horn
• Mains voltage: AC 230 V
• Operating voltage: 21... 28.6 VDC
• Operating current: max. 5 A
• Power supply: 150 W
• Emergency power supply: up to 72 h (optional)
• Battery capacity: 2 x 12 V, 45 Ah
• Plug-in position: 2 -> for serial interfaces RS232, RS4852, 2 -> for network modules, 1 -> for loop extension (C-NET), 5 -> for line or I/O cards (card cage)
• Operating temperature: -8... +42 °C
• Storage temperature: -20... +60 °C
• Relative humidity: 95% (no condensation)
• Protection category: IP30
• Color housing/cover: grey, RAL 7035/grey, RAL-Design 050 00 00
• Cabinet dimensions (W x H x D): 430 x 796 x 260 mm (without cover cap) 430 x 796 x 288 mm (with cover cap)
|